« Playing safe by getting expert advice. »
Securiton - our philosophy, our services, your benefits.

« B3 REL16E »


B3 REL16E

The module contains 16 bi-stable, freely programmable 24 V/3 A relay contacts and is used for controlling sirens, holding magnets, relays etc. Whether the contact is a make or break contact is determined by software-based programming. By programming a fail-safe position the status of every individual relay can be defined in the event of a supply voltage failure or the fire alarm control panel being switched off. A module of type B5-BAF or B5-MRI16 must be fitted to connection slot 9 of the SecuriFire module rack for controlling the relays. The B3-REL16 can only be used in slot 11 to 13.